Date | Status | Code | Description | Ref | Location | Comments |
8/22/2017 | Transfer | Correct Below | * | | Access to Game Stop feeder breaker. | Tennant required to have a key to th locked electrical room housing the feeder breaker. Mall management to provide letter stating that tennant will have posession of the key. |
8/22/2017 | Transfer | Correct Below | * | | Engineering / plans. | Engineer needs to verify correct source of supply for Game Stop tennant panel. Label panel as to source of supply. Label Game Stop feeder breaker with correct space / suite number. |
8/22/2017 | Transfer | Correct Below | * | | Rooftop condenser unit. | 1-line dwg shows a new, 30A, non-fused disconnect, protected by a 30A breaker. Label disconnect as to source of supply and space served. Labelling must be suitable forthe environment. (Existing fused disc. does not have working clearances, cannot determine fuse sizes. EGC not bonded to enclosure, 40A breaker supplies unit.) |
8/22/2017 | Transfer | Correct Below | * | | Sales floor. | (2) EM battery back-up troffers not functioning in emergency mode. EM battery packs on order. (2) other EM troffers are functioning. AFD may not approve a conditional final with (2) of (4) EM lights functioning. |