Date | Status | Code | Description | Ref | Location | Comments |
10/16/2012 | | EF1 | Correct Below | | Bar area orangew recept for receipt printer and TV recept not GFCI protected. | |
10/16/2012 | | EF1 | Correct Below | | Break room recepts need GFCI (floor drain and contiguous with kitchen). | |
10/16/2012 | | EF1 | Correct Below | | update panel schedules: make each circuit designation unique. | |
10/16/2012 | | EF1 | Correct Below | | Roof top items: could not find priors. | |
10/16/2012 | | EF1 | Correct Below | | Dishwasher fed from (2) circuits: No disconnects at machine. No marked off on appliance. No placcarding to show (2) sources of power. | |
10/16/2012 | | EF1 | Correct Below | | Remote exterior heads. | |
10/16/2012 | | EF1 | Correct Below | | Exterior landscape lighting, etc. | |