Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 173380
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Requested by: Tommy Meade 232-9213 frank@alyeskaelectric.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/24/2012TransferEF1Correct Below Bar area orangew recept for receipt printer and TV recept not GFCI protected. 
9/24/2012TransferEF1Correct Below Break room recepts need GFCI (floor drain and contiguous with kitchen). 
9/24/2012TransferEF1Correct Below update panel schedules: make each circuit designation unique. 
9/24/2012TransferEF1Correct Below Roof top items: could not find priors. 
9/24/2012TransferEF1Correct Below Dishwasher fed from (2) circuits: No disconnects at machine. No marked off on appliance. No placcarding to show (2) sources of power. 
9/24/2012TransferEF1Correct Below Remote exterior heads. 
9/24/2012TransferEF1Correct Below Exterior landscape lighting, etc. 
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS